Single steam system

Single steam system, SSS

up to 560 kg/h or 380 kW
Single steam system, SSS
Boiler type
SSS 160 SSS 260 SSS 360 SSS 460 SSS 560
Unit type
Single unit
Single unit Single unit Single unit Single unit
Steam boiling up to
160 kg/h
260 kg/h
360 kg/h 460 kg/h 560 kg/h
Thermal load up to
110 kW 175 kW 245 kW 315 kW 400 kW
Thermal output up to
105 kW 170 kW 235 kW 300 kW 380 kW
Max. operating pressure
13 bar (overpressure)
13 bar (overpressure) 13 bar (overpressure) 13 bar (overpressure) 13 bar (overpressure)
Warming up time
8 Min.
8 Min.
8 Min.
8 Min.
8 Min.
Max. oil throughput
9,2 kg/h
14,6 kg/h 20,5 kg/h 26,5 kg/h 32,6 kg/h
Max. as throughput
10,6 m3/h 17 m3/h 23,7 m3/h 30,5 m3/h 37,7 m3/h
Gas flow pressure min.
20 mbar
20 mbar 20 mbar 20 mbar 
20 mbar 
Gas connection
1"
1"
1"
1"
1"
Exhaust mass flow
0,05 kg/s 0,08 kg/s 0,11 kg/s 0,14 kg/s 0,18 kg/s
Exhaust stack D
150 mm
180 mm
180 mm
250 mm
300 mm
Flue draft min.
0,15 mbar
0,15 mbar
0,15 mbar
0,15 mbar
0,15 mbar
El. connection
400 V / 50 Hz
400 V / 50 Hz
400 V / 50 Hz
400 V / 50 Hz
400 V / 50 Hz
El. power consumption
1,5 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
Total weight
580 kg
680 kg
780 kg
1180 kg
1290 kg
Boiler height B
1580 mm
2080 mm 2140 mm 2140 mm 2240 mm
Boiler width C
800 mm 800 mm 800 mm 930 mm 930 mm
Boiler depth F
1380 mm 1590 mm 1590 mm 1690 mm 1690 mm
Installation height A
1250 mm 1420 mm 1590 mm 1590 mm 1590 mm
Installation width
690 mm 800 mm 800 mm 930 mm 930 mm
Installation depth E
780 mm 800 mm 800 mm 930 mm 930 mm
Exhaust stack G
850 mm 1440 mm 1440 mm 1440 mm 1440 mm
Request
Jumag steam generators are not forced flow boilers. There is no excess water. Common fault sources, such as piston pump, transmission, suction and pressure valves, usually required with regular evaporator coil, do not exist.

Instead, the Jumag steam generator works on the same principle as a water room boiler. The burner switches on and off automatically depending on the steam pressure.The boiler feed pump, a maintenance-free rotatory pump, feeds water automatically based on the water level.

Larger output is provided by our multi-boiler system >
Jumag Direkt

Do you still have questions?